P-16-128CF 16 to 128 ZONE COMMERCIAL FIRE CONTROL PANEL

The P-16-128CF is the UL listed commercial fire version of the P-16-128 security control panel. As such, the P-16-128CF has the same system expandability and features as the P-16-128 plus added features and expandability for commercial fire applications as described herein.

Partner Premier SeriesPanel Features

In addition to all of the features of the P-16-128 (see separate spec sheet), the following are additional hardware and software features of the P-16-128CF for use in commercial fire applications :

  • P-16-128CF control panel is supplied in red system cabinet c/w :

    - P4701 fire module

    - 16VAC, 40VA transformer

  • PC4701 fire module includes :

    - 1 Class 'B' / Style 'B' two-wire smoke detector zone accommodating 30 12VDC compatible detectors

    - 1 Class 'B' / Style 'B' waterflow zone

    - two supervised communicator outputs

    - terminal connection for house telephone

    - 1 fire alarm actuated relay… Form'C', rated 2 A, 30VDC

    - 1 fire trouble actuated relay… Form 'C', rated 2 A, 30VDC

  • up to 112 PARTNER-AMS-220 addressable smoke detectors can be added to the system spread over one or both of the addressable loops :

    - addressable fire zones may be programmed as the following types

    - standard fire zones

    - auto-verify fire zones

    - delayed fire zones (for residential only)

  • all hardwired zones on the P-16-128CF can be programmed as fire zones with the following zone types :

    - standard fire zones

    - waterflow zones

    - auto-verify fire zones

    - delayed fire zones (for residential only)

    - fire supervisory zones

  • programmable fire alarm output patterns… steady, temporal pattern, CA pattern, pulsed, or strobe fire.

  • programmable fire bell options… bell cut-off time and fire silence inhibit time.

  • all P4702BP bell outputs are supervised for :

    - short circuit

    - open circuit

    - ground fault

  • alarm autoscroll… displays fire alarms and selected trouble conditions at 2 second intervals on system LCD keypads. Items displayed include :

    - first fire alarm [zone label]

    - fire alarm [zone label]

    - fire supervisory [zone label]

    - fire bell has been silenced

    - bell zone trouble

    - failure to communicate

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

P-16-128CF 16 to 128 ZONE COMMERCIAL FIRE CONTROL PANEL

  • fire drill… activates main bell output and P4702BP fire bell outputs according to their programmed fire signalling modes without activating other functions and without sending reporting codes to the central station. Keypads display "Fire Drill in Progress" during test. If an actual alarm occurs during test, the test is automatically cancelled and the standard fire alarm functions occur.

  • fire inspector test… ensures that all fire initiating devices are communicating and are supervised. All test results are logged to the system event buffer.

  • scheduled smoke detector tests… 50 time/ date smoke detector test schedules programmable by partition… for addressable detectors only

  • lamp test… use keypad to activate annunciator lights for 2 seconds

Partner Premier SeriesSystem Expansion

    In addition to all of the modules available for the P-16-128 (see separate spec sheet), the following are specially designed for use with the P-16-128CF in commercial fire applications :

  • P4702BP fire system bell panel… provides 2 supervised Class'B' / Style'Y' bell outputs c/w battery charger, 28 VAC 170VA transformer, and cabinet with space for two 12 volt 4 Ah sealed lead-acid rechargeable batteries.

  • P-16-128CF fire system quad relay / power supply module… similar to P4204, but c/w battery charger, 16 VAC 40VA transformer, and cabinet with space for two 12volt 7 Ah sealed lead-acid rechargeable batteries.

  • P4612 fire zone annunciator  (1) … 12 zone, surface mount, keypad style, plastic annunciator. Includes common fire zone trouble, fire bell zone trouble, common system trouble, and AC 'on' indicators.

    (1) system can also include P4632 and P4664 thirty two and sixty four zone point / graphic annunciators to annunciate fire zones, security zones, and common system indications.

  • P4350R fire system external battery charger… for longer standby time required by listed fire systems.

  • keypads with red bezels for fire application… at least one PRS 400F must be used with the P-16-128CF

    - keypad piezo buzzer will sound continuously if communication is lost with control panel

    - PRS 400F… same as PRS 400 but with red bezel. Five function keys have fire system specific assignments :

      - Silence Trouble

      - Silence Bells

      - Fire Reset

      - Fire Drill

      - Lamp Test


Partner Premier SeriesElectrical Specifications

  • bell output… 12VDC, 700mA max. continuous...use for burglary only

    - PTC over current protected – self-restoring.

  • AUX+ output… 12VDC, 500mA max.

  • SAUX+ output… 12VDC, 300mA max.

    - SAUX+ output is normally +12VDC and power is removed upon activation. Typically used to reset 4-wire smoke detectors.

    Note… total for AUX+ output and SAUX+ output is 500mA max. e.g. If the SAUX+ output is loaded to 200 mA then only 300mA remains for the AUX+ output.

  • AUX+ and SAUX+ outputs protected by a common PTC over current device which is self-restoring.

  • PGM outputs :

    - as standard PGM outputs… 12VDC, 50mA max. each. PGM outputs are normally unpowered and switch to +12VDC upon activation.

    - as addressable outputs… 12VDC, 170mA max. each

    Note… PGM outputs are individually programmable as addressable loops or as general purpose PGM outputs.

  • Combus… 500mA max. from the P-16-128CF main panel

    - additional power is provided by P4204CF modules. Maximum Combus capacitance is 80nF which is typically 4,000 feet of 22AWG wire. Consult wire Mfg. specifications.

    Note… total loading for the Bell output, AUX+, SAUX+, PGM1, PGM2 and the Combus must not exceed 900mA.

  • battery charger… up to 350mA to charge 12volt lead-acid batteries up to 14Ah capacity. Battery charger is supervised for opens and is protected by PTC over current device which is self-restoring.

  • input power… 16VAC, 40VA

  • ground fault detection… built-in and enabled by connecting earth ground to EGND terminal on PC4020CF main panel.

    Note… maximum power from the P-16-128CF panel power supply may be limited by its ability to maintain the required standby time. The P4350R external battery charger can be used to assure maximum panel loading capability and provide the required standby. See the P-16-128 Installation Manual for panel loading and standby calculations.


Partner Premier SeriesMechanical Specifications

  • operating environment

    - 32 to 122°F (0 to 50°C)

    - 90% RH non-condensing

  • P4050CR red cabinet :

    - surface mount

    - hinged door with screw closure.

    - provision for door keylock

    - provision for door and wall tamper switches.

    - space for two 12volt 7Ah lead-acid rechargeable batteries.

    - 14.8" H x 12.0" W x 4.9"D
    (37.6 x 30.5 x 12.5cm)

Partner Premier SeriesCompatible Smoke Detectors

  • 2-wire smoke detectors

    - DSC...MN220/220T
    - PARTNER...AMS-220/220T addressable

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

Partner Premier SeriesTypical System Arrangement

Typical System Arrangement

Partner Premier SeriesOrdering Information

    P-16-128CF… control panel with fire option c/w:

    - P-16-128CF… main control module

    - P4701... fire module

    - PT1016... transformer

    - P4050CR... red cabinet

    - installation manual, user manual, and programming worksheets

    - module mounting hardware and 32 EOL resistors

    P-16-128CBCF… as P-16-128CF but P4050CRAR attack resistant cabinet with P4050CARC attack resistant inner cover

    Keypads are not supplied with the main panel – at least one fire keypad with red bezel is required per system. Select from the following keypads:

    PRS 400F… alphanumeric keypad with red bezel and 5 function keys

    PRS 400FT… as PRS 400F but with wall tamper switch

    PRS 400/T… are identical to the above but do not have red bezels.


Partner Premier SeriesListings

    USA

    UL864

    ...Control Unit System
      (L, CS, -A, M, SS, WF)

    UL1610

    ...Central Station Burglar Alarm

    UL609

    ...Local Burglar Alarm

    UL365

    ...Police Station Burglar Alarm

    UL985

    ...Household Fire Warning

    UL1023

    ...Household Burglar Alarm

    CANADA

    ULC-S527

    ...Central Station Fire Alarm

    ULC-S302

    ...Central & Monitoring Station Burglar Alarm

    ULC-S303

    ...Local Alarm
      (Commercial Burglary)

    ULC-S310

    ...Household Burglar Alarm

    ULC-S545

    ...Household Fire Warning

    UL294

    ...Access Control