The P4204CF is designed to meet the requirements of UL864 for UL listed commercial fire systems.
Note : the P4204CF is not required in Canada. Use the P4204 in Canada.
The P4204CF is a dual purpose power supply/output module, providing programmable relay outputs for controlling external devices and power to
repower the Combus... to provide additional power as required for downstream devices which are powered off of the Combus:
Supplied in a panel enclosure, the P4204CF contains a standard P4204 module, a 350mA battery charger and a 16VAC 40VA transformer, with remaining
space for two 7Ah batteries and one P4108A hardwired zone expansion module.
|
Note : |
to comply with UL requirements, the rated capacity of the
PC4204CF for repowering the Combus is reduced to 550mA. |
|
- 4 fully programmable high current Form'C' relays with contacts
rated at 2 A @ 30VDC
- provides 550mA @ 12VDC to power direct connected devices or
repower the Combus (based on 24 hour standby with two 7Ah
batteries) (uses relay #1 when repowering Combus)
- complete with supervised battery charger : 12VDC, 350mA charging
current for sealed lead-acid rechargeable batteries
- connect up to 16 modules per system for 64 relays total
- each relay programmable to activate for any of 59 options
- fully supervised for low battery, and aux supply and AC power loss
- connection for external tamper… supervised by system
- connect up to 1,000' (305m) from control panel via COMBUS
- operating environment
- 32 to 122°F (0 to 50°C)
- 90% RH non-condensing
- current draw …30mA (from Combus)
- dimensions …
12"H x 12"W x 4.5"D (30.5 x 30.5 x 11.5cm)
|
|
|
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
|
|
 
|
|
|
Up to 16 P4204CF modules may be installed in
the Combus wherever additional power is required
downstream of the P4204CF for additional
modules and devices powered off of the Combus.
|
|
|
|
|
 
|
|
|
|
|
 
|
|
| |
P4204CF .... |
|
| |
power supply/ relay output module with 4 relay
outputs for fire installations requiring UL864
listing includes: |
|
| - |
P4052CR red cabinet, 12"H x 12"W x 4.5"D
(30.5 x 30.5 x 11.5 cm) |
|
| - |
P4204 module |
|
| - |
PT1016 transformer, 16 VAC, 40VA |
|
| - |
space for two 7Ah, 12volt lead-acid batteries |
|
| - |
space for one P4108A hardwire zone expansion module |
|
|
 
|
|
|
USA |
|
UL864 |
...Control Units System
...(L, CS, -A, M, SS, WF)* |
|
UL1610 |
...Central Station Burglar Alarm |
|
UL609 |
...Local Burglar Alarm
|
|
UL365 |
...Police Station Burglar Alarm
|
|
UL985 |
...Household Fire Warning
|
|
UL1023 |
...Household Burglar Alarm |
|
CANADA |
|
ULC-S527 |
...Central Station Fire Alarm |
|
ULC-S302 |
...Central & Monitoring Station
...Burglar Alarm |
|
ULC-S303 |
...Local Alarm
...(Commercial Burglary) |
|
ULC-S310 |
...Household Burglar Alarm |
|
ULC-S545 |
...Household Fire Warning |
|
UL294 |
...Access Control |
|
|